Datasheet Home \ Datasheet Details
Download
PDF Abstract Text:
CS series
Solid State Hybrid Voltage Sensor
CS series
Solid State Hybrid Voltage Sensor
· Close differential · Choice of two types - Fixed pick-up and knob adjustable drop-out - Knob adjustable pick-up and drop-out · Internal 2 Form C (DPDT) output relay
Fixed Pick-up and Adjustable Drop-out
Adjustable Pick-up and Drop-out
File E22575 File LR15734
Sensing Modes
Engineering Data
Adjustable Voltage Sensor Operation
RELAY ENERGIZED
Ordering Information - Boldface items are stocked.
Fixed Pick-Up and Adjustable Drop-Out
Part Number CSJ-38-71010 CSL-38-31010 Pick-Up (Volts) 105 22 Drop-Out Range (Volts) 90-103 16-21 Maximum Voltage 140VAC (50 / 60 Hz.) 32VDC
VOLTAGE
HYSTERISIS 2 VOLTS
Adjustable Pick-Up and Adjustable Drop-Out
Part Number CSJ-38-70010 CSL-38-30010 CSL-38-40010 CSL-38-60010 Pick-Up Range Drop-Out Range (Volts) (Volts) 92-140 20-30 40-58 92-140 90-138 18-28 38-56 90-138 Maximum Voltage 150VAC (50 / 60 Hz.) 32VDC 60VDC 150VDC
RELAY DE-ENERGIZED
NOTE 1
NOTE 2
Actual maximum drop-out voltage is the selected pick-up voltage less the hysterisis voltage.
Outline Dimensions
.600 MAX. (15.24) 2.937 MAX. (76.60) 1.781 MAX. (42.24) .875 (22.23)
Wiring Diagrams - Bottom Views (pins numbered clockwise from keyway)
Tyco Electronics Corporation - P&B, Winston-Salem, NC 27102 Technical Support Center: 1-800-522-6752, www.pandbrelays.com Specifications and availability subject to change without notice. 13C2755 Printed in U.S.A. IH / 4-00
2.406 MAX. (61.11)
AC INPUT
DC INPUT
|