BE1-50/51B SELF POWERED TIME OVERCURRENT RELAY RETROFIT KITS BE1-


Datasheet Thumbnail

  

Download PDF



Top Searches for this datasheet



BE1-50/51B
BE1-50/51B SELF POWERED TIME OVERCURRENT RELAY RETROFIT KITS
BE1-50/51B Case
BE1-50/51B-219, Retrofit
BE1-50/51B-214, Retrofit
BE1-50/51B Time Overcurrent Relay provides economical overload fault protection generators, transformers, lines motors.
FEATURES APPLICATION Page
ADVANTAGES
Self powered from 50/60Hz systems, available secondaries. field selectable curves. Independent instantaneous overcurrent function. Drawout construction, testable case. Qualified requirements IEEE C37.90-1989, C37.90.1-1989, C37.90.2-1989, UL508 series adds: Patented integrating reset characteristic, even when current goes zero. Replicates electromechanical reset applications. Five additional field selectable curves, total Five year warranty.
FUNCTIONAL DESCRIPTION Pages
SPECIFICATIONS Pages
ADDITIONAL INFORMATION
INSTRUCTION MANUAL
Request Publication 9252000991
RETROFIT INFORMATION Pages ORDERING INFORMATION Pages
RETROFIT INSTRUCTION MANUALS
Request Publication 9252000994 (214, replacement) Request Publication 9252000995 (218 replacement with case) Request Publication 9252000981 (219, replacement)
TIMING CURVES
Request Publication 9252000998 Basler-equivalent curves Request Publication 9252000999 Basler-equivalent BS142 curves
STANDARDS, DIMENSIONS ACCESSORIES
Request Publication
UHD-10 8-02
ROUTE 143, HIGHLAND, ILLINOIS 62249, U.S.A. PHONE 618-654-2341 618-654-2351
BE1-50/51B
FEATURES
field selectable, inverse, fixed time British Standard (BS142) time overcurrent curves series relays series). Instantaneous overcurrent function. Wide setting ranges: Time Overcurrent: 15.9 Unit) 3.18 Unit) Inst. Overcurrent: Unit) 19.8 Unit) Current pickup accuracy Timing accuracy Less than transient overreach. Zero Pickup setting safety during installation. Timed Overcurrent Reset Selectable Instantaneous Decay Characteristic (200 series relays only). burden nominal) self powered from 50/60 systems, utilizes standard secondaries. Drawout construction. Manual method trip circuit testing. Standard magnetically latched targets IOC. Direct reading front panel controls. recognized under standard 508. Qualified requirements -IEEE C37.90.1-1989 SWC. -IEEE C37.90.2-1989 RFI. -IEC 255-5 impulse. Continuous automatic calibration. Time characteristics extend Pickup. Positive visual indication that microprocessor executing code.
APPLICATION
BE1-50/51B single phase self powered, microprocessor based time overcurrent relay. relay designed applications requiring time delayed coordination phase ground overcurrent conditions. relay used provide coordinated protection overhead underground distribution circuits. Other applications include overcurrent back-up protection transformers generators, protection neutral grounding resistors reactors. Since time-current characteristics included within relay, standard relay ordered before coordination study completed, thereby allowing physical construction proceed. series relays have curves that match ABB/Westinghouse time curve shape. series adds five unique GE-type curves. Both series include curves. This also advantage changes system configuration coordination accomplished without hardware change. Models included (200 series) which have memory replicate decaying reset electromechanical relays even when power relay lost. series applications that require coordination with resetting nearby electromechanical relays. instantaneous overcurrent element standard relay. This element designed minimize transient overreach. instantaneous element includes selectable delay characteristics improved coordination with downstream devices customer requirements.
BE1-50/51B
FUNCTIONAL DESCRIPTION
Aux. output provided replacement units. Figure Functional Block Diagram CURRENT INPUT single phase current from Amp, Amp, 50/60 system current transformer (CT) applied BE1-50/51B. This input current provides both power sensing quantity relay. current applied relay provides energy internal power supply. When sufficient current available, Active/Pickup will turn green. applications where circuit loading conditions less than that required illuminate LED, relay remains operable will provide overcurrent protection. sensing input transformer provides quantity scaled measured Time Instantaneous functions. Ranges, ratings, accuracies apply described Table MICROPROCESSOR setting TIME DIAL, TIME CURVE selector switch, circuit board jumpers provide microprocessor with operating parameters desired response relay. microprocessor performs program operations based input current level internal software program. When Active/Pickup green, microprocessor active executing code. Operating power from power supply applied microprocessor supervisor circuit. When input current falls below acceptable level, supervisor circuit interrupts microprocessor halts further operation. watchdog timer monitors microprocessor specific pulses indicating proper program operation. something occurs disrupt microprocessor, these pulses stop, watchdog timer times sends reset pulse microprocessor. microprocessor resets resumes normal operation.
Scaling input signal accomplished separate networks time instantaneous functions. scale factors established front panel pick-up settings. Pickup settings provide maximum sensitivity safety precaution installation process. Pickup will occur when input current level adequate power unit. Table Current Sensing Capabilities
Time Element Time Element 50/60 System Time Element Max. Continuous Max. Current Secondary Pickup Range Current Second 15.9 Amps Amps Amps Steps 3.18 Amps Steps Amps Amps Instantaneous Pickup Range Amps Steps 19.8 Amps Steps
Time Element Pickup Accuracy from 15.9 Amps from 3.18 Amps
Instantaneous Pickup Accuracy from Amps from 19.8 Amps
BE1-50/51B
FUNCTIONAL DESCRIPTION, continued
OUTPUTS TIME contacts 51AUX) closed accordance with conditions defined selected time characteristic equation sensed current magnitude. sensed current exceeds INST PICKUP setting, INST contacts (50) closed. Breakers controlled output contacts manually trip tested inserting jumper between TIME INST MANUAL TRIP test points front panel. TIME ELEMENT CHARACTERISTIC SHAPES BS142 CURVES time characteristic curves follow relation: Time trip MN-C instantaneous reset characteristic forces timer zero when input current falls below setting. This fast reset characteristic prevents ratcheting effect electro-mechanical relay disks that occurs repeated faults. decaying reset characteristic replicates decaying reset electromechanical relay disks. Models with style numbers series continue decaying process even when input current goes zero. Models with style numbers series reset immediately when input current drops below minimum required power-up relay (.5A models 0.1A models). TIME DIAL RANGE ACCURACY TIME DIAL range steps. setting results instantaneous operation without intentional time delay. INSTANTANEOUS ELEMENT CHARACTERISTICS characteristic phase faults faster because relay will powered-up. However, tripping characteristic ground applications slightly longer allow time power-up relay. This longer trip time ground applications beneficial because helps avoid nuisance trips. These timing characteristics shown Figure Additional definite time delays 0.1, seconds added instantaneous element series units; series units have only seconds. definite delay determined switches circuit card. OUTPUTS Separate output contacts provided TIME (51) INST (50) trip functions. additional auxiliary output relay AUX) included. This output operates simultaneously with TIME output relay. output contacts configured normally open (NO). MANUAL TRIP TESTING relay provided with front panel test points allow shorting output terminals verify external control circuit wiring. TARGETS target indicators provided standard feature BE1-50/51B. These magnetically latched, current operated targets provide visual indication trip TIME INST output contact. These targets must manually reset after abnormal condition been removed corrected.
Time decaying reset M2-1 Table
Curve Type Basler Type Short Inverse Short Inverse Long Inverse Long Inverse Definite Inverse Definite Inverse Inverse Inverse Very Inverse Very Inverse Extremely Inverse Extremely Inverse British Standard Very Inverse British Standard Extremely Inverse Fixed Time Similar CO-2 GE-IAC-55 CO-5 IAC-66 CO-6 CO-7 CO-8 IAC-51 CO-9 IAC53 CO-11 142-B 142-C none series only series only
series only series only series only
Actual curve constants available Instruction Manual. page this bulletin applicable publication number. Active/Pickup front panel will turn when applied current just exceeds PICKUP setting (See Figure RESET Reset occurs when current level less than pickup. Internal switch provides selection either Instantaneous decaying reset characteristic.
BE1-50/51B
FUNCTIONAL DESCRIPTION, continued
Figure Instantaneous Characteristics
BS142 curves both series models:
S=Short Inverse L=Long Inverse D=Definite Time M=Moderately Inverse I=Inverse V=Very Inverse E=Extremely Inverse B=BS142 Very Inverse C=BS142 Extremely Inverse F=Fixed Time
Figure Time-Current Characteristics curves series models only: Short Inverse Inverse Very Inverse Extremely Inverse Long Inverse
BE1-50/51B
FUNCTIONAL DESCRIPTION, continued
Figure Front Panel, Case
SPECIFICATIONS
CURRENT SENSING INPUT: Unit Unit
Continuous Current Second Current
TIME PICKUP ACCURACY: setting TIME DIAL RANGE: steps TIME CHARACTERISTICS: Nine inverse time fixed time function selected front panel switch. Characteristic curves defined time characteristic equation. fixed time characteristic provides delays seconds corresponding dial setting.
14.0 Amps Amps
Amps Amps
TIME PICKUP RANGE: Unit: 15.9 Amps steps Unit: 3.18 Amps 0.02 steps TIME DROPOUT: less than pickup value.
BE1-50/51B
SPECIFICATIONS, continued
INVERSE TIMING ACCURACY: cycle multiples pickup from Below multiples errors increase directly proportional value (MN-1) FIXED TIME ACCURACY: milliseconds, whichever greater. TIME RESET: Instantaneous decay, internally selectable. INST PICKUP RANGE: Unit: Amps steps Unit: 19.8 Amps steps INST DROPOUT: pickup INST PICKUP ACCURACY: setting INST CHARACTERISTIC: Figure Additional user selectable switches) definite delays 0.1, seconds -100 series; -200 series. INST TRANSIENT RESPONSE: Less than overreach with system time constants milliseconds. BURDEN: Burden non-linear resistive. Unit: Ohms 0.5A Ohms Unit: Ohms 0.1A Ohms TARGETS: Magnetically latched, manually reset TIME INST output functions. Operate Current: minimum Coil Resistance: Operate Time: millisecond OUTPUTS: (50/51) Resistive: 120/240 Vac: Make carry sec., carry min., continuously, break Amp. 125/250 Vdc: Make carry sec., carry min., continuously, break Amp. OUTPUTS: (AUX) Resistive: 120/240 Vac: Make sec., carry continuously, break Amp. 125/250 Vdc: Make sec., carry continuously, break Amp.
Inductive: 120/240Vac, 125/250Vdc: Make carry sec., carry continuously, break Amp. (L/R=0.04).
ISOLATION: 2000 50/60 minute (1500 minute across open contacts) accordance with 255-5 IEEE C37.90-1-1989 (Dielectric Test). SURGE WITHSTAND CAPABILITY: Qualified IEEE C37.90.1-1989 FAST TRANSIENT: Qualified IEEE C37.90.1-1989 IMPULSE TEST: Qualified 255-5 RADIO FREQUENCY INTERFERENCE (RFI): Qualified IEEE C37.90.2-1989. Field tested using five watt transceiver operating random frequencies centered around MHZ. TEMPERATURE: Operating Range -40° (-40° (158° Recommended Storage Range -50° (-58° (122° SHOCK: each three mutually perpendicular planes. VIBRATION: each three mutually perpendicular planes swept over range total sweeps, minutes sweep. CASE SIZE: WEIGHT: pounds
Inductive: 120/240Vac, 125/250Vdc: Make carry sec., carry min., continuously, break Amp. (L/R=0.04).
BE1-50/51B
RETROFIT FEATURES ADVANTAGES
BE1-50/51B-219/226 Cradle cover
BE1-50/51B-219 -226 retrofit kits consist cradle cover provides installing Basler BE1-50/51B single-phase time overcurrent relay existing case without making wiring changes.
BE1-50/51B-214/225 Cradle, adapter plate cover
BE1-50/51B-214 -225 retrofit kits consist cradle, adapter plate, cover provides installing Basler BE1-50/51B single-phase time overcurrent relay existing case without making wiring changes. BE1-50/51B-218 complete replacement relay with case.
ADVANTAGES
direct replacement drawout cradle. direct replacement drawout cradle. electrical mechanical rework required panels during retrofit. Competitively priced. model replaces more than models listed next page. Patent #5,751,532. Numerous technical advantages: units equipped with instantaneous element. Instantaneous element lower, because relay corrected transient overreach. Therefore, range does need high relay. selectable curves wide pickup ranges. Lower burden extends linear range CTs. Self-calibration feature eliminates need recalibration, thereby reducing maintenance labor.
BE1-50/51B
REPLACEABLE MODELS
These relays self-powered include memory replicate decaying reset electro-mechanical relay disks. models that retrofitted with BE1-50/51B-219:
Curve Short Time Long Time Definite Moderately Inverse Inverse Very Inverse Extremely Inverse
Model Numbers CO-2*11*1N CO-5*11*1N CO-6*11*1N CO7*11*1N CO-8*11*1N CO-9*11*1N CO-11*11*1N
models that retrofitted with BE1-50/51B-214:
Curve Inverse
Model Numbers 12IAC51A***A 12IAC51B***A 12IAC53A***A 12IAC53B***A 12IAC77A***A 12IAC77B***A 12IAC55A***A 12IAC55B***A 12IAC66A**A 12IAC66B**A
Very Inverse
Extremely Inverse
Short Time
Long Time
NOTES: digit covering pickup ranges, instantaneous, non-instantaneous, models. Units with instantaneous elements designated with eighth character model number.
BE1-50/51B
ORDERING
MODEL NUMBER BE1-50/51B Time Overcurrent Relay ORDER: Designate Model Number three-digit dash number from Table define configuration desired. Table DESCRIPTION System Secondaries
Semi-Flush Mounting, Size Case Drawout Construction, Testable-in-Case Projection Mounting, Size Case Drawout Construction, Testable-in-Case Semi-Flush Mounting, Size Case Drawout Construction, Testable-in-Case BE1-50/51B-105 BE1-50/51B-205 BE1-50/51B-106 BE1-50/51B-206 BE1-50/51B-107 BE1-50/51B-207
MODEL NUMBER (NOTE)
System Secondaries
Semi-Flush Mounting, Size Case Drawout Construction, Testable-in-Case Projection Mounting, Size Case Drawout Construction, Testable-in-Case Semi-Flush Mounting, Size Case Drawout Construction, Testable-in-Case BE1-50/51B-101 BE1-50/51B-201 BE1-50/51B-102 BE1-50/51B-202 BE1-50/51B-103 BE1-50/51B-203
Table DESCRIPTION RETROFITS System Secondaries
Retrofit relays Cradle plugs into existing case. Adapter plate cover included. Complete replacement relay with same terminal connections units. style case. Retrofit relays. Cradle plugs into existing case. cover provided. BE1-50/51B-214
MODEL NUMBER (NOTE)
BE1-50/51B-218
BE1-50/51B-219
System Secondaries
Retrofit relays Cradle plugs into existing case. Adapter plate cover included. Retrofit relays Cradle plugs into existing case. cover provided. BE1-50/51B-225
BE1-50/51B-226
NOTE: Model numbers ending series include memory replicate decaying reset characteristic electromechanical
relay disks even while input current zero. Model numbers ending series reset instantaneously (regardless settings) when input current drops below minimum pickup value.
BE1-50/51B
NOTES
ORDERING INFORMATION units self powered supplied with switch selectable curves, TIME INST functions outputs, magnetically latched targets, auxiliary output contact. STANDARD ACCESSORIES: test plug available allow testing relay without removing external wiring. Order test plug: Basler part number: 10095.
BE1-50/51B
ROUTE 143, 269, HIGHLAND, ILLINOIS U.S.A. 62249 P.A.E. Pins, 67319 Wasselonne Cedex FRANCE PHONE 618-654-2341 618-654-2351 PHONE (33-3-88) 87-1010 (33-3-88) 87-0808 http://www.basler.com, info@basler.com

Other recent searches


SAA2023 - SAA2023   SAA2023 Datasheet
MAS6279 - MAS6279   MAS6279 Datasheet
KM736FV4011A - KM736FV4011A   KM736FV4011A Datasheet
KM718FV4011A - KM718FV4011A   KM718FV4011A Datasheet
KDZ11EV - KDZ11EV   KDZ11EV Datasheet
ACTF070094 - ACTF070094   ACTF070094 Datasheet

 

Privacy Policy | Disclaimer
© 2012 Datasheet Archive