G3PA / G3PB
Long Service Life for Circuits that Cycle Frequently
G3PA / G3PB
Long Service Life for Circuits that Cycle Frequently
Solid State Relays (SSRs)
Built-in heat sink increases life and reliability Voltage turn-on at zero crossing reduces initial inrush load currents LED indicator turns on when control power is applied DIN rail mountable Conforms to UL, CSA, VDE and CE requirements
Ordering Information
J G3PA Relays with Replaceable Triac Output Cartridge
D D Current indicator turns red when excessive current is applied Side-by-side dense mounting is possible using built-in linking brackets
Single-Phase Models
Stock Note: Shaded models are normally stocked. Max. load current 10 amps 20 amps 40 amps 60 amps 20 amps 30 amps 50 amps Max. inrush current 150 amps, 60 Hz 220 amps, 60 Hz 440 amps, 60 Hz 440 amps, 60 Hz 220 amps, 60 Hz 440 amps, 60 Hz 440 amps, 60 Hz 12-24 VDC 200-480 VAC Operating voltage 5-24 VDC Load voltage 24-240 VAC Model G3PA-210B-VD DC5-24 G3PA-220B-VD DC5-24 G3PA-240B-VD DC5-24 G3PA-260B-VD DC5-24 G3PA-420B-VD-2 DC12-24 G3PA-430B-VD-2 DC12-24 G3PA-450B-VD-2 DC12-24
J G3PB Relays
Single Phase Models
Stock Note: Shaded models are normally stocked. Max. load current 15 amps 25 amps 35 amps 45 amps Max. inrush current 150 amps, 60 Hz 220 amps, 60 Hz 440 amps, 60 Hz 440 amps, 60 Hz Operating voltage 12-24 VDC Load voltage 100-240 VAC Model G3PB-215B-VD DC12-24 G3PB-225B-VD DC12-24 G3PB-235B-VD DC12-24 G3PB-245B-VD DC12-24
Solid State Relays
G3PA / G3PB
J DIN Rail Mounting Track
Stock Note: Shaded models are normally stocked. Description DIN rail track, 7.3 mm (0.29 in) depth 50 cm (1.64 ft) length DIN rail track, 7.3 mm (0.29 in) depth 1 m (3.28 ft) length End plate Spacer PFP-50N PFP-100N PFP-M PFP-S Model
J Replacement Parts
Stock Note: Shaded models are normally stocked. Name Power device cartridge 10 A Carry current Applicable SSR G3PA-210B-VD DC5-24 G3PA-210BL-VD DC5-24 G3PA-210-VD AC24 20 A G3PA-220-VD DC5-24 G3PA-220L-VD DC5-24 G3PA-220-VD AC24 40 A G3PA-240-VD DC5-24 G3PA-240L-VD DC5-24 G3PA-240-VD AC24 60 A G3PA-260-VD DC5-24 G3PA-260L-VD DC5-24 G3PA-260-VD AC24 20 A 30 A 20 A 30 A 50 A G3PA-420-VD DC12-24 G3PA-430-VD DC12-24 G3PA-420-VD-2 DC5-24 G3PA-430-VD-2 DC5-24 G3PA-450-VD-2 DC5-24 Model G32A-A10-VD DC5-24 G32A-A10L-VD DC5-24 G32A-A10-VD AC24 G32A-A20-VD DC5-24 G32A-A20L-VD DC5-24 G32A-A20-VD AC24 G32A-A40-VD DC5-24 G32A-A40L-VD DC5-24 G32A-A40-VD AC24 G32A-A60-VD DC5-24 G32A-A60L-VD DC5-24 G32A-A60-VD AC24 G32A-A420-VD DC12-24 G32A-A430-VD DC12-24 G32A-A420-VD- DC5-2 -24 G32A-A430-VD- DC5-2 -24 G32A-A450-VD- DC5-2 -24
Application Examples
Temperature Controller SSR
Load Voltage output terminal (for driving SSR) Heater
Input
Output
Power supply for load
Direct connection possible
D D D Longer service life with no contacts to wear out Reduced electromagnetic interference Faster response time D D D Vibration and shock resistance No audible noise when switching Enhanced reliability
Solid State Relays
G3PA / G3PB
Specifications
J Ratings
Input (at 25°C)
Model G3PA-210B-VD G3PA-220B-VD G3PA-240B-VD G3PA-260B-VD G3PA-420B-VD-2 G3PA-430B-VD-2 G3PA-450B-VD-2 G3PB-215B-VD G3PB-225B-VD G3PB-235B-VD G3PB-245B-VD 12 to 24 VDC 9.6 to 30 VDC 7 mA max. 9.6 VDC max. 1 VDC min. 12 to 24 VDC 9.6 to 30 VDC 7 mA max. 9.6 VDC max. 1 VDC min. Rated voltage g 5 to 24 VDC Voltage range g g 4 to 30 VDC Input current p impedance i d 7 mA max. Voltage level Must operate voltage 4 VDC max. Must release voltage 1 VDC min.
Output
Model Load voltage G3PA-210B-VD G3PA-220B-VD G3PA-240B-VD G3PA-260B-VD G3PA-420B-VD-2 G3PA-430B-VD-2 G3PA-450B-VD-2 G3PB-215B-VD G3PB-225B-VD G3PB-235B-VD G3PB-245B-VD 75 to 264 VAC (50 / 60 Hz) H ) 180 to 528 VAC (50 / 60 Hz) H ) 19 to 264 VAC (50 / 60 Hz) H ) Load current 0.1 to 10 A 0.1 to 20 A 0.5 to 40 A 0.5 to 60 A 0.5 to 20 A 0.5 to 30 A 0.5 to 50 A 0.1 to 15 A 0.1 to 25 A 0.5 to 35 A 0.5 to 45 A Applicable load Inrush current 150 A (60 Hz, 1 cycle) 220 A (60 Hz, 1 cycle) 440 A (60 Hz, 1 cycle) 440 A (60 Hz, 1 cycle) 220 A (60 Hz, 1 cycle) 440 A (60 Hz, 1 cycle) 440 A (60 Hz, 1 cycle) 150 A (60 Hz, 1 cycle) 220 A (60 Hz, 1 cycle) 440 A (60 Hz, 1 cycle) 440 A (60 Hz, 1 cycle) With Class-1 AC resistive load 2.4 kW at 240 VAC 4.8 kW at 240 VAC 9.6 kW at 240 VAC 14.4 kW at 240 VAC 9.6 kW at 480 VAC 14.4 kW at 480 VAC 24 kW at 480 VAC 3 kW at 200 VAC 5 kW at 200 VAC 7 kW at 200 VAC 9 kW at 200 VAC
Solid State Relays
G3PA / G3PB
J Characteristics
Item Operate time Release time Output ON voltage drop Leakage current I 2t Insulation resistance Dielectric strength Vibration resistance Shock resistance Ambient temperature Approved standards Ambient humidity Weight G3PA210B-VD G3PA220B-VD G3PA240B-VD G3PA260B-VD G3PA420B-VD-2 G3PA430B-VD-2 G3PA450B-VD-2
Part number Operate time Release time Output ON voltage drop Leakage current Permissible I2t (half 60-Hz wave) Insulation resistance Dielectric strength Vibration resistance Shock resistance Ambient temperature Approved standards G3PB-215B-VD G3PB-225B-VD G3PB-235B-VD G3PB-245B-VD
1 / 2 of load power source cycle + 1 ms max. (DC input) 1 / 2 of load power source cycle + 1 ms max. (DC input) 1.6 V (RMS) max. 10 mA max. (at 200 VAC) 121 A2s 260 A2s 1, 260 A2s 100 M min. at 500 VDC 2, 500 VAC, 50 / 60 Hz for 1 min Destruction and malfunction: 10 to 55 Hz, 0.75-mm double amplitude Destruction: 294 m / s2 Malfunction: 294 m / s2 (DIN track mounting) Operating: Storage: -30°C to 80°C (with no icing or condensation) -30°C to 100°C (with no icing or condensation)
Ambient humidity Weight